Annicom Axio Logo  
    +44(0)1420487788  
 
home | about us | products | datasheets | account
 
   
datasheetdetails
 <<  |  <  |   AX-ADFPT - Air Flow
AX-ADFPT-1K-D / Air Diff Pressure & Flow Transmitter, LCD, 0-1000 Pa POA Qty
AX-ADFPT-2K-D / Air Diff Pressure & Flow Transmitter, LCD, 0-2000 Pa POA Qty
AX-ADFPT-5K-D / Air Diff Pressure & Flow Transmitter, LCD, 0-5000 Pa POA Qty
AX-ADFPT-7K-D / Air Diff Pressure & Flow Transmitter, LCD, 0-7000 Pa POA Qty
Add suffix “-40” after part number for -40 ºC cold resistant / POA Qty
Add Suffix “-AZ” after part number for Autozero Calibration / POA Qty
 <<  |  <  | OVERVIEW | SPECIFICATION | DATASHEETS        

The AX-ADFPT is used for measuring volume flow, velocity, and static and differential pressure of air and noncombustible gases in order to monitor and control building automation, HVAC and cleanroom systems. The AX-ADFPTcan be connected directly to the pressure measurement points in a centrifugal fan, providing accurate flow measurement of the fan providing enables easy selection of settings according to the selected fan or in-duct measurement probe.
Product Features
Power Supply: 24Vac or 24Vdc, ±10%
Output: Voltage 0-10V or 2-10V, min. resistance 1kΩ
Current 4-20mA, min. load 20Ω, max. load 500Ω
Accuracy: 1K and 2K: Pressure < 125 Pa = 1 % + ±2 Pa , Pressure > 125 Pa = 1 % + ±1 Pa
5K and 7K: Pressure < 125 Pa = 1.5 % + ±2 Pa , Pressure > 125 Pa = 1.5 % + ±1 Pa
Overpressure: Proof: 25kPa
Burst: 30kPa
Pressure Connection: Ø5mm and Ø6.3mm ABS connectors
Electrical Connection: Screw terminals suitable for cables 0.2-1.5mm²
Response Time: 1.0−20 s, selectable via menu
Zero Point Calibration: Automatic autozero, manual pushbutton
Compatible Media: Dry air or non-aggressive gases
Display : 2-line display (12 characters/line )
Line 1: Volume or velocity measurement
Line 2: Pressure measurement
Pressure Units (select via menu): Pa, kPa, mbar, inWC, mmWC
Flow Units (select via menu): Volume: m3/s, m3/hr, cfm, l/s, none
Velocity: m/s, ft/min
Protection Standard: IP54
Operating Environment: Temperature: -20°C to 50°C ( Temperature compensated range: 20°C to 50°C )
-40°C to 50°C ( Low temperature model)
-5°C to 50°C ( Models with Auto Zero calibration)
Humidity: 0 to 95 % RH, non condensing
Country of Origin: Finland



AX-ADFPT.pdf / Air Differential Pressure Switch